Specifications
It has high mechanical and abrasion resistance. It is easy to clean, dust free, hygienic and antibacterial. It provides economical solution in use. It has very good adhesion property. If required, a detailed chemical resistance table can be requested from our sios technical service.
Usage areas
Sios epoxy self leveling ANT Areas where electronic equipment is used excessively, such as operating theaters, hospital labs, electrical and electronic labs, aircraft hangars, painting shops, computer rooms, automobile factories.
Surface Quality
The concrete surface should be clean, sound and of sufficient compressive strength (at least 25 N / mm2), with a pull off strength of at least 1.5 N / mm2. should be free. The slurry layer on the surface must be removed. (Shot-Blast, Rota Tiger, Milling etc.)
Surface Preparation
Concrete surfaces should be prepared to obtain an open porous surface by removing the cement grout using abrasive equipment. Weak concrete should be removed, voids and holes should be fully exposed. All dust, loose and loose particles should be removed from the floor with a brush and / or vacuum cleaner before the product is applied. Concrete cracks and false joints should be cleaned. Surface repairs, filling blowholes / holes, cracks repair, false joints are important.
Method of Application
First of all, A and B components are mixed thoroughly separately. Then the B component is added into the A component and mixed for a minimum of 3 minutes until it becomes homogeneous. The resulting mixture is applied to the floor with a notched trowel and air bubbles in the mixture are removed with the help of a spiked roller. Copper busbars are mounted on this surface in order to increase conductivity and transmit the static tension to the ground. The copper strip thickness to be used should not be more than 50 microns. Copper bars must be adhered to the ground very well. Overlapping busbars should be connected to each other by electrically soldering. Then, these busbars should be combined and connected to the business ground. • In the absence of operational grounding, the grounding electrode should be hammered or the grounding plate should be buried only for this system.
Consumption
Total theoretical consumption is 1.8-2 kg / m2.
Packaging
It is offered in 18 (A) + 4 (B) KG Metal packages.
Shelf life
It can be stored for a maximum of 12 months in closed areas at temperatures between + 5C and + 25C in its unopened original package. Opened material should be used as soon as possible.
Security Alert
During the application, no smoking and work should be done away from naked flames in well-ventilated areas. Hands and eyes should be protected with gloves and protective glasses. In case of material contact with eyes, eyes should be washed with plenty of water. Adequate ventilation is required during application. Ask your dealer for Safety Data Sheet (MSDS).